Structure Scope of Work Dashboard |
|||||||
Builder Name: |
|||||||
Project: |
|||||||
Project Start Date: |
Scopes of Work issued: |
||||||
GoTo |
Scope of Work Phase |
Issued to |
Contact |
|
Phone |
Date |
|
Structure Subcontractor List |
|||||
Phase |
Subcontractor Business Name |
Contact |
Phone |
|
|
Project: |
||||||||||||
Provided to: |
Email: |
|||||||||||
Contact: |
Phone: |
|||||||||||
Date: |
||||||||||||
Objective of this Scope of Work |
||||||||||||
■ To ensure foundations and concrete walls are built to engineering specifications or better and are plumb, square, and level. |
||||||||||||
Terms used in this document |
||||||||||||
■ Site Superintendent: shall refer to any Company representative with authority to enforce this Scope of Work. |
||||||||||||
■ SUBCONTRACTOR: shall refer to the Subcontractor's organization, its employees, or any representative of the Subcontractor assigned the authority to perform per this Scope of Work. |
||||||||||||
Acceptable Performance |
||||||||||||
Foundation: General |
||||||||||||
■ A new set of plans is required for each house. Plans are subject to changes and modifications. |
||||||||||||
■ It is the responsibility of the Subcontractor to have the new plans before beginning work. |
||||||||||||
■ The Subcontractor will correct any errors that occur from using an incorrect set of plans at no cost to Company. |
||||||||||||
■ Foundations shall be built per plan and/or engineer’s specifications. |
||||||||||||
■ Concrete shall be placed at an appropriate rate so that it can be spread, straightened, and finished properly. |
||||||||||||
■ Concrete should not be allowed to run or be worked over long distances, and should not be allowed to drop more than 4'-0". |
||||||||||||
■ Holes left by nails or line pins should be pointed while adjacent concrete is green. |
||||||||||||
■ Poured concrete should not crack in excess of 1/8" in vertical or horizontal displacement. |
||||||||||||
■ Concrete shall not pit, scale, or spall to the extent that the aggregate is exposed. |
||||||||||||
■ If temporary power is not yet connected to the lot, the Subcontractor must furnish a generator. |
||||||||||||
■ Permission of the Site Superintendent is required for drawing electricity or water from an adjacent jobsite. |
||||||||||||
■ All trash and debris shall be removed from lot to dumpster or the designated trash area. |
||||||||||||
■ All runoff concrete shall be removed to the driveway cut. |
||||||||||||
■ No invoice will be paid until all required work is field-measured and verified. |
||||||||||||
■ Payment will be based on the field measurements and not on the amount of concrete delivered to the site. |
||||||||||||
■ Any items found during the final inspection that need correction shall be corrected before payment will be made. |
||||||||||||
Foundation: Footings |
||||||||||||
■ Prior to digging footings, the Subcontractor and the Site Superintendent shall verify all the dimensions of the house. |
||||||||||||
■ Prior to digging footings, the Subcontractor and the Site Superintendent shall verify all offsets are staked. |
||||||||||||
■ Prior to digging footings, the Subcontractor and the Site Superintendent shall verify all lines are straight and true. |
||||||||||||
■ The Subcontractor shall verify with the Site Superintendent that the staked area of the house will fit on the lot. |
||||||||||||
■ The Subcontractor shall verify with the Site Superintendent that the house is within the building lines and any easements. |
||||||||||||
■ Forms shall be set per plan. |
||||||||||||
■ All footings for stoops and porches shall be dug and poured as a part of the foundation for the house. |
||||||||||||
■ The Subcontractor shall dig all footings. Footings may be dug by machine or by hand. |
||||||||||||
■ Footings should not be over-dug, and must be of width and depth to accommodate the amount of concrete listed below. |
||||||||||||
■ Footings shall be poured a minimum of 16" wide by 8" deep for single-story structure. |
||||||||||||
■ Footings shall be poured a minimum of 16" wide by 8" deep for a two-story structure or a single-story structure on a basement. |
||||||||||||
■ Footings shall be poured a minimum of 18" wide by 8" deep for a three-story structure or two-story structure on a basement. |
||||||||||||
■ All footings measurements provided above are subject to engineering reports and requirements. |
||||||||||||
■ Two #4 rebar shall be installed continuously in all footings at mid-point of the depth of the footing. |
||||||||||||
■ Bending and cutting of reinforcing steel is to be done by the Subcontractor. Additional rebar may be required for engineered footings. |
||||||||||||
■ The top surface of footings shall be level, all corners shall be square, and all footings shall be straight. |
||||||||||||
■ The bottom surface of footings may not have a slope exceeding 1" in 10". |
||||||||||||
■ Footings shall be stepped where necessary to change the elevation of the top surface of the footings. |
||||||||||||
■ Footings shall be stepped where the slope of the bottom surface of the footing will exceed 1" in 10". |
||||||||||||
■ Footings shall be installed per engineered design. |
||||||||||||
■ All concrete strength ratings shall be per engineered design. |
||||||||||||
■ Footings shall pass all required inspections prior to the placement of forms for poured walls and stem walls. |
||||||||||||
Foundation: Poured Walls and Stem Walls |
||||||||||||
■ Concrete walls shall be a minimum of 8" in width or larger as otherwise specified in the engineer’s specifications. |
||||||||||||
■ At minimum, #4 rebar reinforced steel shall be placed vertically 6'-0" OC and horizontally 3'-0" OC throughout the foundation wall area. |
||||||||||||
■ The above rebar specifications are subject to engineering and code requirements, and specifications in the plan documents. |
||||||||||||
■ The Subcontractor is responsible for supplying and setting anchor bolts in all poured walls. |
||||||||||||
■ Bolts shall be 1/2"-diameter anchor bolts placed 6'-0" on center and not more than 12 " from corners. |
||||||||||||
■ Bolts shall extend a minimum of 15" into masonry or 7" into concrete. |
||||||||||||
■ Anchor bolts shall have a clear height of 2-3/4" for 2x framing - 1/8" sill seal + 1 1/2" bottom plate + 1 1/8" minimum nut and washer. |
||||||||||||
■ All walls shall be true, plumb, and square. Concrete walls shall not be out of plumb more than 1/2" in 8'-0". |
||||||||||||
■ Concrete walls should not vary more than 1/2" out of square when measured along the diagonal of a 9'-0" x 12'-0" x 15'-0" triangle at any corner. |
||||||||||||
■ Concrete wall variance should not exceed 1/4" out of level in 20'-0", with no ridges or depressions in excess of 1/4" within any 32' measurement. |
||||||||||||
■ Poured concrete foundation walls shall not leak. |
||||||||||||
■ There shall be no honeycombs. |
||||||||||||
■ Concrete walls shall maintain structural integrity and not crack in excess of 1/8" in width or displacement. |
||||||||||||
■ Concrete poured at temperatures at or below 32 degrees Fahrenheit (F) shall contain 2-percent calcium. |
||||||||||||
■ Any concrete walls poured in conditions that have the potential for frost shall be covered with polyethylene for protection against frost damage. |
||||||||||||
Other |
||||||||||||
Subcontractor acceptance or rejection (required): |
||||||||||||
(initial) |
I have read, understand, accept, and will comply with this Scope of Work |
|||||||||||
I do not accept this Scope of Work |
||||||||||||
Signing on behalf of Subcontractor |
Date of completion |
|||||||||||
Project: |
||||||||||||
Provided to: |
Email: |
|||||||||||
Contact: |
Phone: |
|||||||||||
Date: |
||||||||||||
Objective of this Scope of Work |
||||||||||||
■ To ensure exterior and interior framing of the house is built to plan specifications, is plumb, square, and level, and meets all code requirements for structural soundness. |
||||||||||||
Terms used in this document |
||||||||||||
■ Site Superintendent: shall refer to any Company representative with authority to enforce this Scope of Work. |
||||||||||||
■ SUBCONTRACTOR: shall refer to the Subcontractor's organization, its employees, or any representative of the Subcontractor assigned the authority to perform per this Scope of Work. |
||||||||||||
Acceptable Performance |
||||||||||||
Framing Labor is divided into multiple sections. This Scope of Work covers all sections. |
||||||||||||
Framing Labor: General |
||||||||||||
■ The framing Subcontractor is responsible for ensuring that the house is framed per plan with all dimensions correct, work plumb and square. |
||||||||||||
■ The quality of the work of subsequent Subcontractors depends in large part on the quality of the framing Subcontractor’s work. |
||||||||||||
■ A new set of plans is required for each house. Plans are subject to changes and modifications. |
||||||||||||
■ It is the responsibility of the Subcontractor to have the most current plans before beginning work. |
||||||||||||
■ The Subcontractor, at no cost to Company, will correct any errors that occur from using an non-current set of plans. |
||||||||||||
■ Company must rely on the Subcontractor to note any incorrect features found during framing. |
||||||||||||
■ Should an error be found, please notify the Site Superintendent immediately so that corrections may be made. |
||||||||||||
■ The Subcontractor will be furnished with a copy of the material order for the job. |
||||||||||||
■ If any items are missing or substituted the Site Superintendent should be informed immediately. |
||||||||||||
■ All work is to be done by trained, experienced individuals. |
||||||||||||
■ Notching, drilling, and cutting of framing members compromise the structural integrity of the house. |
||||||||||||
■ Under no circumstances shall roof or floor trusses be cut, notched, or otherwise damaged. |
||||||||||||
■ The Subcontractor shall keep the waste of materials to a minimum. |
||||||||||||
■ Wasted or damaged materials will, at the Site Superintendent's discretion, be charged to the Subcontractor. |
||||||||||||
■ All nails are to be firmly set. No bent nails shall protrude into or onto any area that will receive door casings, drywall, or other types of finish. |
||||||||||||
■ The framing Subcontractor is responsible for boring the necessary holes in the bottom plate to accommodate anchor bolts. |
||||||||||||
■ The framing Subcontractor is responsible for the completion of the anchor bolt installation with washers and nuts. |
||||||||||||
■ All foundation vents shall be installed in appropriate locations and quantities by Subcontractor. |
||||||||||||
■ Safety bracing shall be installed around all interior openings with drops of more than 24". |
||||||||||||
■ All exterior openings with a drop of more than 24" shall be blocked by crossbars running horizontally at 24" and 36" across the opening. |
||||||||||||
■ Framing and sheathing members shall be fastened according to code and manufacturer’s instructions. |
||||||||||||
■ Drywall backing shall be installed throughout the house to ensure proper installation of drywall. |
||||||||||||
■ Subcontractor shall install adequate nailing surface at windows, doors, exterior corners, and other areas to ensure solid anchorage. |
||||||||||||
■ Subcontractor shall install lateral blocking at shower stalls, wall cabinet locations, and bathroom fixture locations. |
||||||||||||
■ All firestops shall be installed per code (chimney chases, under tubs, around showers, etc.). |
||||||||||||
■ The Subcontractor is responsible for setting temporary stairs before beginning the next level. |
||||||||||||
■ Temporary handrails shall be installed on all stairs. |
||||||||||||
■ It is the responsibility of the Subcontractor to install all trusses correctly according to the layout furnished with the trusses and to plan. |
||||||||||||
■ Thresholds shall be braced before the job is complete. |
||||||||||||
■ All temporary bracing, except safety bracing, shall be removed at the completion of the framing. |
||||||||||||
■ Extra material will be stacked in the garage. The Site Superintendent, with the Subcontractor, will inventory the excess material. |
||||||||||||
■ The extra material inventory list shall be attached to the Work Order and invoice when submitted for payment. |
||||||||||||
■ All trash and building debris shall be removed to the dumpster or to an area designated by the Site Superintendent. |
||||||||||||
■ The house shall be broom-swept before job shall be considered complete. |
||||||||||||
■ The house must pass all framing inspections before the framing labor will be considered complete. |
||||||||||||
■ All labor for any corrections required by the framing inspectors will be at the expense of the Subcontractor. |
||||||||||||
■ Any items found during the final inspection that need correction shall be corrected before payment will be made. |
||||||||||||
Framing Materials |
||||||||||||
■ All bottom plates where the wall is to sit on concrete shall be pressure-treated wood. |
||||||||||||
■ Inder no circumstances shall material that is not pressure treated come in contact with concrete. |
||||||||||||
■ All framing materials should be of appropriate size, species, and grade to meet building code and engineering requirements. |
||||||||||||
■ Lumber that is inferior in terms of condition or structural integrity shall not be installed. |
||||||||||||
Framing Labor: Floors |
||||||||||||
■ Floor system variance should not exceed 1/4" out of level in 20'-0". |
||||||||||||
■ Floor system should have no ridges or depressions in excess of 1/8" within any 32" measurement. |
||||||||||||
■ Floor trusses shall be installed per the manufacturer’s layout. |
||||||||||||
■ Subfloor panels shall be installed with long direction perpendicular to joists, and with staggered end joints. |
||||||||||||
■ Floor sheathing shall be level and securely attached to supports to provide an adequate base to receive finish flooring and fasteners. |
||||||||||||
■ All subflooring shall be installed with a 1/8" gap between pieces to allow for swelling due to the absorption of moisture. |
||||||||||||
■ Any buckling of the subfloor shall be planed, sanded, and smoothed by the framer. |
||||||||||||
■ All subflooring gaps larger than 1/8" shall be filled with acceptable filler, then smoothed and sanded. |
||||||||||||
■ All subflooring shall be glued and screwed immediately after the application of the adhesive. |
||||||||||||
■ The Subcontractor shall repair any subflooring that squeaks, creaks, or gives due to improper installation. |
||||||||||||
■ No subflooring shall float at joints or squeak overall. |
||||||||||||
■ A “bright” is a nail driven through a bottom plate of a wall that is not driven into a structural member of the floor system. |
||||||||||||
■ Brights are a major source of floor squeaks. |
||||||||||||
■ All brights must be hammered over from the underside of the floor sheeting to clench the nail.. |
||||||||||||
Framing Labor: Walls General |
||||||||||||
■ Studs, plates, cripples, and headers shall be cut squarely and within 1/8" of required length. |
||||||||||||
■ Wall layout measurement variance shall not exceed 1/8" in 20'-0". |
||||||||||||
■ Bearing walls shall not exceed 1/4" out of level in 20'-0". |
||||||||||||
■ Bearing walls shall not have more than a 1/8" ridge or depression within any 32" measurement. |
||||||||||||
■ Bearing walls shall not be more than 1/2" out of level over the entire bearing surface. |
||||||||||||
■ To check for square, mark 8'-0" out of the corner down one wall and 6'-0" out of the corner down the other wall. Marks should be exactly 10'-0" apart. |
||||||||||||
■ Interior and exterior walls shall not vary more than 1/4" out of square when measured along the diagonal. |
||||||||||||
■ See image below for how the measurement is to be taken. |
||||||||||||
■ Walls shall not be more than 1/8" out of plumb in any 48" vertical measurement. |
||||||||||||
■ No warped studs shall be used. |
||||||||||||
■ All top plates shall be doubled 2x material, except when using Advanced Framing techniques. |
||||||||||||
■ All headers shall be true and level using appropriate material. |
||||||||||||
■ Window and door headers shall conform to code requirements and be installed crown up. |
||||||||||||
■ Window and doors should be checked with a level for jamb squareness and straightness. |
||||||||||||
■ Minimum 1x4 (2x6 preferred) blocking shall be cut-in in kitchen when wall cabinets will not be hung from the top plate. |
||||||||||||
■ For 30” high cabinets on all walls, blocking height is at 84” oc. |
||||||||||||
■ For 42” cabinets on 9’-0" or higher walls, blocking height is 96” oc. Other heights must be confirmed with job superintendent. |
||||||||||||
■ Garden tub and tub/shower units shall be placed inside the bath areas before the bathrooms are framed. |
||||||||||||
■ All framing for bathrooms shall be completed only after the tub units are inside. |
||||||||||||
■ If the Subcontractor is setting windows and exterior doors, Window and Exterior Door Installation Scope of Work shall pertain. |
||||||||||||
■ Window and exterior door installation will be checked using the Window and Exterior Door Installation inspection report. |
||||||||||||
■ Exterior doors and windows shall be installed level, plumb, and square in the opening. |
||||||||||||
■ Exterior doors and windows shall have no more than a 1/4" in 48" deviation in any direction. |
||||||||||||
■ Windows and doors should be installed so that they operate properly as intended and with reasonable ease. |
||||||||||||
Framing Labor: Walls Exterior |
||||||||||||
■ Sill sealer insulation shall be installed in all exterior walls and in walls separating the house from the garage. |
||||||||||||
■ Sill sealer shall extend slightly on each side of a plate. It must be visible for all inspections. |
||||||||||||
■ All exterior walls on concrete stem walls shall be attached within 12” of bottom plate breaks. |
||||||||||||
■ All exterior walls shall be constructed of the appropriate studs set 16" on center. |
||||||||||||
■ Exterior sheathing shall be installed according to manufacturer’s instructions. |
||||||||||||
■ No broken pieces of sheathing shall be left in place. No gaps or missing pieces shall be allowed. |
||||||||||||
■ Exterior wall sheathing shall be smooth, securely attached to supports, and shall provide an adequate base to receive siding and fasteners. |
||||||||||||
■ All window and door openings shall be level, plumb, square, and built to the correct rough opening size as specified by the manufacturer. |
||||||||||||
■ Individual garage doors shall have appropriate header material installed. |
||||||||||||
■ Headers must be completely and securely resting on, and fastened to, supporting jacks. |
||||||||||||
■ If the plans call for brick, the brick lintel must be installed so that it reaches the outside edge of the supporting jacks. |
||||||||||||
■ Sliding glass doors shall be framed per the manufacturer’s rough opening specifications. |
||||||||||||
■ All exterior corner walls shall be braced. |
||||||||||||
■ All exterior hung door openings, including garage-to-house doors, shall be framed 2 7/8” over in height and 2” over in width. |
||||||||||||
Framing Labor: Header Construction |
||||||||||||
■ For standard loads, headers for openings less than 48" shall be minimum (2) 2 x 6 Douglas fir or MicroLam. |
||||||||||||
■ For standard loads, headers for openings 48" - 71" shall be minimum (2) 2 x 8 Douglas fir or MicroLam. |
||||||||||||
■ For standard loads, headers for openings 72" - 95" shall be minimum (2) 2 x 10 Douglas fir or MicroLam. |
||||||||||||
■ For standard loads, headers for openings 96" + shall be minimum (2) 2 x 12/equal Douglas fir or MicroLam. |
||||||||||||
■ For non-standard loads, headers for openings will be per engineering. |
||||||||||||
Framing Labor: Walls Interior |
||||||||||||
■ Interior walls bottom plates shall be fastened through to supporting structural members whenever possible. |
||||||||||||
■ When interior wall bottom plates are fastened to floor sheathing only, nails must be clenched from underneath. |
||||||||||||
■ Interior non-load-bearing walls shall be constructed of 2x studs set to a maximum of 24" on center. |
||||||||||||
■ If the plans call for interior load-bearing walls, the framing members for such walls shall be set 16" on center. |
||||||||||||
■ Basement load-bearing walls shall be 2x6 studs set 16" on center. |
||||||||||||
■ All interior hung door openings shall be framed 2 1/2” over in height and 2” over in width. |
||||||||||||
■ All bi-fold door openings shall be framed 1 ½” over in height and 1 1/2” over in width. |
||||||||||||
■ All bypass door openings shall be framed 2” over in height and 0” over in width. |
||||||||||||
■ All pocket door openings shall be framed 4½” over in height and 2 x callout size plus 2” in width. |
||||||||||||
■ Minimum 1x4 (2x6 preferred) blocking shall be cut-in in baths for the placement of bath hardware. |
||||||||||||
■ Blocking for towel bars shall be centered at 43" above sub-floor. |
||||||||||||
■ Blocking for grab bars shall be centered at 37" above sub-floor. |
||||||||||||
■ Blocking for toilet paper holders shall be centered at 24" above sub-floor. |
||||||||||||
■ Blocking for towel rings shall be centered at 54" above sub-floor. |
||||||||||||
■ If the water heater tank is located in the open garage area, Subcontractor is required to enclose the area of the hot water tank. |
||||||||||||
■ The Subcontractor is required to frame two walls, with the third wall being the house wall. |
||||||||||||
■ One wall must protect the hot water tank from impact or damage by an automobile. |
||||||||||||
Framing Labor: Roof |
||||||||||||
■ Trusses shall be set as per layout from truss manufacturer. |
||||||||||||
■ Particular attention shall be paid to “Top” stamp and bearing tags. |
||||||||||||
■ All joist hangers shall be installed and nailed with a nail in each hanger hole. |
||||||||||||
■ No truss may be cut, notched, nicked, or otherwise damaged. |
||||||||||||
■ If any truss is accidentally damaged the Site Superintendent should be notified immediately. |
||||||||||||
■ No truss may be repaired without the approval of the manufacturer’s engineer. |
||||||||||||
■ Roof structural members should be installed securely and be within 1/4" of plumb from collar tie to top of ridge. |
||||||||||||
■ Ridge shall not vary more than 1/4" out of level plus or minus over the entire length. |
||||||||||||
■ Roof ridge beam deflection shall be no greater than 1/2" in 8'-0". |
||||||||||||
■ Roof sheathing shall be smooth, securely attached to supports, and shall provide an adequate base to receive roofing fasteners. |
||||||||||||
■ Roof sheathing shall not bow more than 1/4" in 24". |
||||||||||||
■ Gable ends shall be completely sheathed. |
||||||||||||
■ Wind bracing shall be installed at gable ends. |
||||||||||||
■ Attic access holes and/or disappearing stairs shall be framed at locations shown on plan or as directed by Site Supervisor. |
||||||||||||
■ Attic access holes shall be framed to a minimum of 20" wide x 30" long. |
||||||||||||
■ Where the plans call for the HVAC unit to be placed in the attic, the Subcontractor must frame a minimum 20" by 30" access. |
||||||||||||
■ A passageway from the access hole to the area of the HVAC unit must be a minimum of 22" by 30". |
||||||||||||
■ The passageway must have a minimum 22" wide floor. |
||||||||||||
■ Flooring shall extend a minimum width of 30" along the control side of the equipment with a 30" high clear working space on all sides. |
||||||||||||
■ If two units are to be installed in the attic the flooring area must be increased to accommodate two units. |
||||||||||||
■ Roof ventilation holes shall be cut per plans. |
||||||||||||
■ Ridge ventilation, if installed, requires that sheathing be held back 2" from ridge line on both sides of ridge. |
||||||||||||
■ Confirm ridge ventilation with Site Supervisor. |
||||||||||||
Other |
||||||||||||
Subcontractor acceptance or rejection (required): |
||||||||||||
(initial) |
I have read, understand, accept, and will comply with this Scope of Work |
|||||||||||
I do not accept this Scope of Work |
||||||||||||
Signing on behalf of Subcontractor |
Date of completion |
|||||||||||
Project: |
||||||||||||
Provided to: |
Email: |
|||||||||||
Contact: |
Phone: |
|||||||||||
Date: |
||||||||||||
Objective of this Scope of Work |
||||||||||||
■ To ensure that Deck and Porch materials are installed in a manner consistent with all applicable building codes, manufacturer's instructions and warranty requirements, and acceptable construction practices. |
||||||||||||
Terms used in this document |
||||||||||||
■ Site Superintendent: shall refer to any Company representative with authority to enforce this Scope of Work. |
||||||||||||
■ SUBCONTRACTOR: shall refer to the Subcontractor's organization, its employees, or any representative of the Subcontractor assigned the authority to perform per this Scope of Work. |
||||||||||||
Acceptable Performance |
||||||||||||
Framing Labor: Deck-Porch - General |
||||||||||||
■ All decks and porches shall meet or exceed all county, state, and federal building codes for safety. |
||||||||||||
■ Trained, experienced personnel shall perform all work. |
||||||||||||
■ The Subcontractor and all employees shall follow all OSHA safety requirements. |
||||||||||||
■ The Subcontractor and all employees shall follow OSHA safety requirements regarding the use of scaffolding. |
||||||||||||
■ All work shall meet or exceed local, state, and national safety standards for decks, deck landings, and deck stairs. |
||||||||||||
■ Local, state, or national safety codes shall take precedence over any item below should such items be in conflict. |
||||||||||||
■ Any item constructed by the Subcontractor shall meet or exceed the safety requirements of local, state, or federal authorities. |
||||||||||||
■ The Subcontractor is responsible for the repair or correction of any item that fails any safety codes. |
||||||||||||
■ The Subcontractor shall correct any movement in stairs, deck rails, and pickets that exceeds the allowable limits of state or local codes. |
||||||||||||
■ The Subcontractor shall replace any wood that splits due to incorrect installation. |
||||||||||||
■ Any work determined to be of poor quality shall be repaired or replaced by the Subcontractor at no cost to Company. |
||||||||||||
Framing Labor: Deck-Porch - Details and Installation |
||||||||||||
■ A new set of plans is required for each house. Plans are subject to changes and modifications. |
||||||||||||
■ It is the responsibility of the Subcontractor to have the new plans before beginning work. |
||||||||||||
■ The Subcontractor will correct any errors and replace damaged materials from using an incorrect set of plans at no cost to Company. |
||||||||||||
■ Company will furnish all materials. |
||||||||||||
■ The Subcontractor shall keep waste material to a minimum. |
||||||||||||
■ Any unnecessary waste or damage to materials will, at Site Superintendent's discretion, be charged to the Subcontractor. |
||||||||||||
■ Decks shall be built to plan. |
||||||||||||
■ Decking material that has excessive splits (light visible through splits or splits that penetrate more than half of the board) shall not be used. |
||||||||||||
■ Decking material that is warped, twisted, or otherwise more than 1/4" out of level shall not be used. |
||||||||||||
■ All unusable material shall be counted and noted as to type and quantity on the Work Order. |
||||||||||||
■ Unusable materials shall be stacked and stored safely for return to supplier. |
||||||||||||
■ Deck or porch ledgers will be bolted to the house using 1/2" through-bolts. Lag bolts are not acceptable. |
||||||||||||
■ If nails are specified, all nails will be ring-shank nails. No nail heads shall protrude from the decking. |
||||||||||||
■ Screws shall be of sufficient length to penetrate into structural members to a depth of 1-1/2". |
||||||||||||
■ No screw heads shall protrude from the decking. |
||||||||||||
■ The spacing on opposite sides of individual deck boards shall not differ in average width by more than 1/8". |
||||||||||||
■ No point on the deck surface shall vary more than 1/2" from any other surface point within 10'-0" on a line parallel to the house. |
||||||||||||
■ Landings shall be installed as required by safety codes. |
||||||||||||
■ Step run and rise shall be per plan. If plan does not specify this information, discuss with Site Superintendent. |
||||||||||||
■ All pickets shall be nailed securely and without splitting. |
||||||||||||
■ All handrails will be tight and secure with no give, shaking, or movement. |
||||||||||||
■ Railings on decks shall not contain slivers longer than 1/8" in exposed areas. |
||||||||||||
■ All construction debris must be removed to the dumpster or to an area designated by the Site Superintendent. |
||||||||||||
■ The job will not be considered complete and payment will not be issued until all trash and debris have been so removed. |
||||||||||||
■ Any items found during the final inspection that need correction shall be corrected before payment will be made. |
||||||||||||
Other |
||||||||||||
Subcontractor acceptance or rejection (required): |
||||||||||||
(initial) |
I have read, understand, accept, and will comply with this Scope of Work |
|||||||||||
I do not accept this Scope of Work |
||||||||||||
Signing on behalf of Subcontractor |
Date of completion |
|||||||||||
Project: |
||||||||||||
Provided to: |
Email: |
|||||||||||
Contact: |
Phone: |
|||||||||||
Date: |
||||||||||||
Objective of this Scope of Work |
||||||||||||
■ To ensure that Stairs are built and installed in a manner consistent with all applicable building codes, manufacturer's instructions and warranty requirements, and acceptable construction practices. |
||||||||||||
Terms used in this document |
||||||||||||
■ Site Superintendent: shall refer to any Company representative with authority to enforce this Scope of Work. |
||||||||||||
■ SUBCONTRACTOR: shall refer to the Subcontractor's organization, its employees, or any representative of the Subcontractor assigned the authority to perform per this Scope of Work. |
||||||||||||
Acceptable Performance |
||||||||||||
Framing Labor: Stairs - General |
||||||||||||
■ Due care must be taken when removing temporary stairs and installing the permanent stairs. |
||||||||||||
■ The installers must not damage the existing framing or other Subcontractors’ work. |
||||||||||||
■ All stairs are to be properly braced on the underside of the stairs to prevent any bouncing, creaks, squeaks, and movement. |
||||||||||||
■ All shims and bracing pieces on the underside of treads must be secured with both additional shims and nails. |
||||||||||||
■ All stairs shall be covered with rosin paper to protect the stair treads during the remaining time of construction. |
||||||||||||
■ All areas of oak on the stair treads shall be doubly protected with a material that cannot be easily removed. |
||||||||||||
Framing Labor: Stairs - Installation |
||||||||||||
■ The Subcontractor shall remove temporary stairs and place them in the garage when permanent stairs are installed. |
||||||||||||
■ The Subcontractor shall prevent damage to existing framing or other completed construction. |
||||||||||||
■ The Subcontractor shall construct stairs in such a manner that stairs do not squeak, creak, bounce, or move. |
||||||||||||
■ The Subcontractor shall add additional bracing as required to ensure the stability of the stairs. |
||||||||||||
■ The Subcontractor shall field-measure the stair area to ensure a correct fit and correct riser spans. |
||||||||||||
■ Stairs are to be fitted to the floor correctly for the floor covering used (wood, vinyl, or carpet). |
||||||||||||
■ Stairways shall not be less than 36" in clear width. |
||||||||||||
■ The greatest riser height within any flight of stairs shall not exceed the smallest riser height by more than 3/8". |
||||||||||||
■ The greatest tread width within any flight of stairs shall not exceed the smallest tread width by more than 3/8". |
||||||||||||
■ When risers are closed, all treads shall have a uniform projection not to exceed 1-1/2". |
||||||||||||
■ The Subcontractor is responsible for cleaning up all residual materials before the job shall be accepted as complete. |
||||||||||||
■ Any items found during the final inspection that need correction shall be corrected before payment will be made. |
||||||||||||
Other |
||||||||||||
Subcontractor acceptance or rejection (required): |
||||||||||||
(initial) |
I have read, understand, accept, and will comply with this Scope of Work |
|||||||||||
I do not accept this Scope of Work |
||||||||||||
Signing on behalf of Subcontractor |
Date of completion |
|||||||||||
Project: |
||||||||||||
Provided to: |
Email: |
|||||||||||
Contact: |
Phone: |
|||||||||||
Date: |
||||||||||||
Objective of this Scope of Work |
||||||||||||
Terms used in this document |
||||||||||||
■ Site Superintendent: shall refer to any Company representative with authority to enforce this Scope of Work. |
||||||||||||
■ SUBCONTRACTOR: shall refer to the Subcontractor's organization, its employees, or any representative of the Subcontractor assigned the authority to perform per this Scope of Work. |
||||||||||||
Acceptable Performance |
||||||||||||
Template: General |
||||||||||||
Template: Details |
||||||||||||
Subcontractor acceptance or rejection (required): |
||||||||||||
(initial) |
I have read, understand, accept, and will comply with this Scope of Work |
|||||||||||
I do not accept this Scope of Work |
||||||||||||
Signing on behalf of Subcontractor |
Date of completion |
|||||||||||
Project: |
||||||||||||
Provided to: |
Email: |
|||||||||||
Contact: |
Phone: |
|||||||||||
Date: |
||||||||||||
Objective of this Scope of Work |
||||||||||||
Terms used in this document |
||||||||||||
■ Site Superintendent: shall refer to any Company representative with authority to enforce this Scope of Work. |
||||||||||||
■ SUBCONTRACTOR: shall refer to the Subcontractor's organization, its employees, or any representative of the Subcontractor assigned the authority to perform per this Scope of Work. |
||||||||||||
Acceptable Performance |
||||||||||||
Template: General |
||||||||||||
Template: Details |
||||||||||||
Subcontractor acceptance or rejection (required): |
||||||||||||
(initial) |
I have read, understand, accept, and will comply with this Scope of Work |
|||||||||||
I do not accept this Scope of Work |
||||||||||||
Signing on behalf of Subcontractor |
Date of completion |
|||||||||||
Project: |
||||||||||||
Provided to: |
Email: |
|||||||||||
Contact: |
Phone: |
|||||||||||
Date: |
||||||||||||
Objective of this Scope of Work |
||||||||||||
Terms used in this document |
||||||||||||
■ Site Superintendent: shall refer to any Company representative with authority to enforce this Scope of Work. |
||||||||||||
■ SUBCONTRACTOR: shall refer to the Subcontractor's organization, its employees, or any representative of the Subcontractor assigned the authority to perform per this Scope of Work. |
||||||||||||
Acceptable Performance |
||||||||||||
Template: General |
||||||||||||
Template: Details |
||||||||||||
Subcontractor acceptance or rejection (required): |
||||||||||||
(initial) |
I have read, understand, accept, and will comply with this Scope of Work |
|||||||||||
I do not accept this Scope of Work |
||||||||||||
Signing on behalf of Subcontractor |
Date of completion |
|||||||||||
Project: |
||||||||||||
Provided to: |
Email: |
|||||||||||
Contact: |
Phone: |
|||||||||||
Date: |
||||||||||||
Objective of this Scope of Work |
||||||||||||
Terms used in this document |
||||||||||||
■ Site Superintendent: shall refer to any Company representative with authority to enforce this Scope of Work. |
||||||||||||
■ SUBCONTRACTOR: shall refer to the Subcontractor's organization, its employees, or any representative of the Subcontractor assigned the authority to perform per this Scope of Work. |
||||||||||||
Acceptable Performance |
||||||||||||
Template: General |
||||||||||||
Template: Details |
||||||||||||
Subcontractor acceptance or rejection (required): |
||||||||||||
(initial) |
I have read, understand, accept, and will comply with this Scope of Work |
|||||||||||
I do not accept this Scope of Work |
||||||||||||
Signing on behalf of Subcontractor |
Date of completion |
|||||||||||
Project: |
||||||||||||
Provided to: |
Email: |
|||||||||||
Contact: |
Phone: |
|||||||||||
Date: |
||||||||||||
Objective of this Scope of Work |
||||||||||||
Terms used in this document |
||||||||||||
■ Site Superintendent: shall refer to any Company representative with authority to enforce this Scope of Work. |
||||||||||||
■ SUBCONTRACTOR: shall refer to the Subcontractor's organization, its employees, or any representative of the Subcontractor assigned the authority to perform per this Scope of Work. |
||||||||||||
Acceptable Performance |
||||||||||||
Template: General |
||||||||||||
Template: Details |
||||||||||||
Subcontractor acceptance or rejection (required): |
||||||||||||
(initial) |
I have read, understand, accept, and will comply with this Scope of Work |
|||||||||||
I do not accept this Scope of Work |
||||||||||||
Signing on behalf of Subcontractor |
Date of completion |
|||||||||||